Distribution Box for Motor Star-Delta (Y-Δ) Reduced-Voltage Starting Control
Distribution Box for Motor Star-Delta (Y-Δ) Reduced-Voltage Starting Control
Product details
Product Introduction
Instruction Manual for Motor Star-Delta (Y-Δ) Reduced-Voltage Starting Control  
Applicable Object: Three-phase asynchronous motor (power ≥ 11kW, voltage 380V/50Hz)  
I. Starting Principle and Purpose  
1. Necessity of Reduced-Voltage Starting  
When the motor power is relatively large (usually ≥ 11kW), direct starting will generate an impact current of 6~8 times the rated current, leading to:  
- A sudden drop in grid voltage (affecting other equipment)  
- Mechanical impact (damaging couplings/belts)  
- Misoperation of protection devices  
2. Principle of Star-Delta Conversion
Starting phase
Winding connection 
Phase voltage  
Starting current  
Starting torque  
Star (Y)
Ends of windings short-circuited  
220V  
1/3 of direct starting current  
1/3 of direct starting torque  
Delta (Δ)
Head and tail connected in sequence
380V
Full-voltage rated current
100% rated torque
Transition time: Usually set to 4~15 seconds (adjust according to load inertia), ensuring that the speed reaches 75%~85% of the rated speed before switching to Δ operation.  
II. System Composition and Component Selection  
1. List of Core Components
Components  
Example models  
Specification Requirements  
Quantity
Main circuit breaker  
Main circuit breaker  
NM1-225S/3300  
1
AC contactor  
CJX2-6511 (Δ operation)  
AC-3 category, current ≥ I<sub>N</sub>  
3
Thermal relay  
R36-160J  
Setting current ≈ I<sub>N</sub> (to prevent false tripping during Y-start)  
1
Time relay  
ST3PF (digital type)  
Range 0.1~999s, accuracy ±1%  
1
Button
LA38-11
Green (start) / Red (stop)
2
2. Protection Function Configuration  
- Short-circuit protection: Main circuit breaker (instantaneous tripping)  
- Overload protection: Thermal relay (only connected to the Δ circuit to avoid misoperation in the Y phase)  
- Voltage loss protection: Contactor self-locking circuit  
- Mechanical interlock: Normally closed contacts of KM<sub>Y</sub> and KM<sub>Δ</sub> are connected in series (to prevent simultaneous attraction)  
III. Electrical Wiring Diagram and Action Logic  
1. Main Circuit Wiring (see attached drawing)  
mermaid  
graph LR  
    L1/L2/L3 --> QF[Main Circuit Breaker] --> KM1[Main Contactor]  
    KM1 --> |U1/V1/W1| KM<sub>Y</sub>[Star Contactor] --> Short-circuit W2/U2/V2  
    KM1 --> |U1/V1/W1| KM<sub>Δ</sub>[Delta Contactor]  
2. Control Circuit Action Process  
mermaid  
sequenceDiagram  
    participant SB1 as Stop Button  
    participant SB2 as Start Button  
    participant KT as Time Relay  
    participant KMY as Star Contactor  
    participant KMΔ as Delta Contactor  
    participant KM1 as Main Contactor  
    SB2->>+KT: Press start → KT is energized and starts timing  
    KT-->>KMY: Instantly pull in (star starting)  
    KMY-->>KM1: Auxiliary contact pulls in (main circuit is energized)  
    KT->>-KMΔ: Timing ends → Disconnect KMY  
    KT-->>+KMΔ: Simultaneously pull in KMΔ (switch to delta)  
    KMΔ-->>KM1: Maintain self-locking  
> Key Wiring Notes:  
> - The 6 motor terminals (U1/U2, V1/V2, W1/W2) must be correctly marked;  
> - The output wires of KM<sub>Δ</sub> must be crossed strictly according to the phase sequence (U1-W2, V1-U2, W1-V2).  
IV. Commissioning Steps and Parameter Settings  
1. No-load Commissioning Process
Steps  
Operation  
Expected phenomena  
1Disconnect the main circuit and only test the control circuit  
KM<sub>Y</sub> pulls in, KT starts timing  
2Simulate the KT time expiration  
KM<sub>Y</sub> releases, KM<sub>Δ</sub> pulls in  
3Connect to the main circuit (motor unloaded)
Y starting current ≤ 1.5I<sub>N</sub>, no impact during switching
2. Setting Principles for Time Relay  
- Light load (fans/water pumps): 4~8 seconds  
- Heavy load (crushers/compressors): 10~15 seconds  
- Formula reference: `t = (√J × N<sub>rated</sub>)/(9.55 × T<sub>Y start</sub>)`  
  (J - Moment of inertia in kg·m²; T<sub>Y start</sub> - Star starting torque in N·m)  
V. Common Faults and Troubleshooting
Fault phenomena  
Possible causes  
Troubleshooting methods  
Tripping during startup  
KM<sub>Y</sub>/KM<sub>Δ</sub> pull in simultaneously  
Check mechanical interlocks and wiring  
Severe vibration during switching  
Conversion time is too short  
Extend KT setting time (in +2-second steps)  
Malfunction of thermal relay  
Overload protection in Y phase takes effect  
Move the thermal relay to the output terminal of KM<sub>Δ</sub>  
Wrong motor rotation direction
Phase sequence of main circuit is reversed
Swap any two incoming phase lines
VI. Safety Warnings  
1. Live working is strictly prohibited: The main circuit breaker must be disconnected and voltage must be verified before switching contactors;  
2. Modification of interlocks is forbidden: Removing the KM<sub>Y</sub>-KM<sub>Δ</sub> interlock may cause short circuits and explosions;  
3. Mandatory grounding requirements: The motor housing and cabinet PE busbar must be reliably grounded (grounding resistance ≤ 4Ω).  
> Compliance Standards:  
> - GB/T 14048.4 "Low-Voltage Switchgear and Controlgear"  
> - IEC 60947-4-1 Contactors and Motor Starters  
Appendix: [Star-Delta Reduced-Voltage Starting Wiring Diagram (CAD Drawing No.: YDQ-2023-STD)](Example Link)  
Note: Before actual application, it is necessary to verify the selection of components according to the motor nameplate parameters (power, current, connection method) and calculate the protection settings.  
VII. Sample diagrams are for reference only

Contact

Leave your information and we will contact you.

About us

Customer services

Contact us 

Tel:13808375766

TEL